START-UP
|
||||||
PLEASE NOTE: Consult factory for optional coated evaporator coils, required for acidic or abnormal conditions. If system is equipped with oil level sight glass the level should be 1/2 to 3/4 of the way up. If oil level is low, add correct oil to compressor. DO NOT OVERFILL. If necessary, temporarily by-pass fan delay control, to run fans until temperature is lowered. Be sure expansion valve is properly set to provide correct amount of superheat. Pour water in drain pan to check proper drainage. Heavy moisture loads may be encountered when starting system for the first time. If coil temperature is below freezing, this will cause a rapid build-up of frost, during initial pull down. Manual defrosting may be required.
|
||||||
|